Product Details:

Place of Origin: China
Brand Name: Noker
Certification: CCC、CE
Model Number: NK300-J3-008

Payment & Shipping Terms:

Minimum Order Quantity: 1 Set
Price: To be discussed later
Packaging Details: Carton Packaging
Delivery Time: 5-8 work days
Payment Terms: L/C, T/T, Western Union
Supply Ability: 1000 set per month
Detailed Product Description
Communication: Modbus RTU Size: Compact Size, Light Weight
Convenient: Keypad Outgoing Start_mode: A Variety Of Motor Starting Modes
Patent: Multiple Patent Technology Protection Frequency: 50/60Hz
High Light:

scr soft starter

,

thyristor soft starter

                                               Electric Motor 7.5 Kw Soft Starter Three Phase AC380V / 660V Space Saving
 

Intelligent motor soft starter, the use of intelligent digital control; With the single chip processor as the intelligence center, thyristor module for actuators for full automatic control motor. It applies various squirrel-cage asynchronous motor control of load, the motor can smooth starting under any working conditions, protect the drag system, reduce the starting current impact on power grid, ensure reliable motor starting.

Smoothly soft stopping function can effectively solve the inertial system surge problem, eliminate the drag system of inertial impact, that is traditional equipment cannot be achieved. Intelligent digital motor soft start equipment system with the complete protection function, extend the service life of the system, reduce the cost of system cost, improve the reliability of system and compatible with all the functions of starting equipment; It is a new ideal alternative for traditional star triangle starter and self-coupling decompression starter.

 
Conditions Of Usage

 

Item Description
Power supply AC220V/380V/660V±15%
Power frequency 50/60Hz
Adaptive Motor Squirrel-cage three-phase asynchronous motor
Starting times It is recommended not to exceed 20 times per hour
Control mode

1) Operation panel control;
2) Operation panel +external control;
3) External control ;

4) External control+ COM control ;
5) Operation panel +external+ COM control;
6) Operation panel + COM control;

7) COM control ;
8) No start or stop operation;

Start Mode

1) Current-limiting start;
2) Voltage ramp start;
3) Torque control +current-limiting to start;

4) Torque control +voltage ramp to start;
5) Current ramp to start;
6) Voltage current-limiting double closed-loop start;

Stop Mode 1) Soft stop;
2) Free stop;

 

 

 

 

 

 

 

Protective Function

1) Open loop protection for external instantaneous stop terminals;

2) Over-heat protection for soft starter;
3) Protection for too long starting time;

4) Input open phase protection;
5) Output open phase protection;
6) Unbalanced three-phase protection;

7) Starting over current protection;
8) Running overload protection;
9) Under voltage protection for power voltage;

10) Overvoltage protection for power voltage;
11) Protection for fault parameter setting;
12) Load short circuit protection;

13) Auto restart or incorrect wiring protection;
14) Incorrect wiring protection of external control stop terminals;

Protection Class IP00,IP20
Cooling Pattern Natural wind cooling
Place to be used Indoor location with good ventilation free from corrosive gas and conductive dust.
Environment Condition Below 2000M. Rise the rate power when the altitude is more than 2000M.
Ambient Temperature -25+45°C
Ambient Humidity 95%(20°C±5°C)
Vibration<0.5G

 

Terminals
 

Terminal No. Name of terminal Description

 

Main circuit

R,S,T Power Supply terminal Connect to Power supply
L11,L12,L13 Bypass terminal Connect to Bypass contactor
U,V,W Motor terminal Connect to motor

 

 

 

 

 

 

 

 

Control circuit

1 Bypass output Bypass output
2
3 Time-delay output Time-delay output
4
5 Failure output Failure output
6
7 Instantaneous stop Instantaneous stop
8 Stop Stop disconnect to Public, then stop
9 Start-up Start-up connect to Public, then start
10 Public Public
11 Analog output - 4-20mA
12 Analog output +

 
Dimension
 

 Electric Motor 7.5 Kw Soft Starter Three Phase AC380V / 660V Space Saving

Electric Motor 7.5 Kw Soft Starter Three Phase AC380V / 660V Space Saving


Maintenance


1. Dust: If too much dust, it will reduce the insulation level of the soft starter, even causes the soft starter does not work.
Brush the dust with clean and dry brush.
Remove dust with compressed air machine.
2. Condensation: If condensation, it will reduce the insulation level of soft starter, even causes the soft starter does not work.
(1) Blow it with a hair dryer or electric stove.
(2) Bring it to power distribution room for dehumidification.
3. Regularly check components' intact. Whether it can work properly.
4. Check soft starter' cooling channel, ensure they are not clogged by dirt and dust.
Before maintenance checking, it has to cut off all power in the line side of soft starter.