logo
Send Message
Home > products >
Medium And High Voltage Soft Start Cabinet
>
6KV 10KV 400KW Medium voltage Anchorwill High voltage Anchorwill motor Solid state soft starter device cabinet

6KV 10KV 400KW Medium voltage Anchorwill High voltage Anchorwill motor Solid state soft starter device cabinet

Product Details:
Place of Origin: CHINA
Brand Name: Anchorwill
Certification: CE
Model Number: MT830
Detail Information
Place of Origin:
CHINA
Brand Name:
Anchorwill
Certification:
CE
Model Number:
MT830
Product Name:
High Voltage Solid State Soft Starter
Standard:
GB3906,IEC298
Main Line Voltage:
3kV-12kVAC -15%+10%
Low Voltage Commissioning:
Function For Low Voltage Testing Of Components
Fiber Optic Triggering:
Fiber Optic Triggering, Complete Isolation Of High And Low Voltage Components
Cooling:
Natural Cooling
Environmental Conditions:
- 10℃~40℃;less Than 95%RH;altitude Below 1000 Meters
Control Power Supply:
AC/DC220V
Highlight:

High Light

Highlight:

400KW Medium voltage Anchorwill motor

,

10KV Medium voltage Anchorwill motor

,

10KV Anchorwill motor Soft Starter

Trading Information
Minimum Order Quantity:
1
Packaging Details:
Packing in wooden cases for export
Delivery Time:
1 - 10 days
Payment Terms:
L/C,T/T
Supply Ability:
999
Product Description
6KV 10KV 400KW Medium Voltage Anchorwill High Voltage Solid State Soft Starter Device Cabinet
Product Specifications
Attribute Value
Product name high voltage solid state soft starter
Standard GB3906, IEC298
Main line voltage 3kV-12kVAC -15%+10%
Low Voltage Commissioning Function for low voltage testing of components
Fiber Optic Triggering Fiber optic triggering, complete isolation of high and low voltage components
Cooling natural cooling
Environmental conditions -10℃~40℃; less than 95%RH; altitude below 1000 meters
Control power supply AC/DC220V
Product Overview

The MT830 series high voltage solid state soft starter (hereinafter referred to as soft starter) adopts high performance thyristor and specialized insulation materials combined with modern power electronic control technology. It realizes soft starting, soft stopping, energy saving and various protection functions of the motor, and is specially designed for constant-speed AC motors.

This device features small starting current, smooth starting, and prolongs the service life of motor and starting equipment. It is widely used in various centrifuges, fans, pumps, conveyor belts, and other dragging systems and machinery equipment.

6KV 10KV 400KW Medium voltage Anchorwill High voltage Anchorwill motor Solid state soft starter device cabinet 0
Key Features
  • Adopting solid-state high-voltage high-power components, low heat generation, no noise; fiber optic trigger, high and low voltage isolation
  • Comprehensive protection functions including over-current, overload, over-voltage, under-voltage, phase loss, current imbalance, and more
  • Low-voltage commissioning function for component testing
  • Capacitive absorption network provides over-voltage protection and reduces dv/dt impact
  • Multiple control methods: local, machine-side, DCS, communication remote control
  • Built-in RS485 communication interface with Modbus control protocol
  • 7-inch full-color touch screen with multi-language support and intuitive operation
Advantages for Air Compressors

The high voltage soft start cabinet converts high current starting into progressive starting, offering several benefits for air compressors:

  • Reduces starting current, avoiding instantaneous excessive current and lowering grid load
  • Extends equipment lifespan by reducing mechanical pressure during startup
  • Improves operational efficiency by preventing mechanical component wear
Technical Specifications
Basic Parameters
Parameter Specification
Load Type Three-phase asynchronous motors, synchronous motors
Main line voltage 3kV-12kVAC -15%+10%
Frequency 50/60Hz ±2%
Power module 12SCRs, 18SCRs, 30SCRs
Phase sequence No phase sequence requirement
Protection Functions
Protection Type Specification
Overcurrent protection 0-600%Ie, 0-60S
Phase loss protection Trip protection for mains phase loss
Overload protection 1.05%Ie-10%Ie class protection
Phase sequence protection Locking the phase sequence of initial installation
6KV 10KV 400KW Medium voltage Anchorwill High voltage Anchorwill motor Solid state soft starter device cabinet 1 6KV 10KV 400KW Medium voltage Anchorwill High voltage Anchorwill motor Solid state soft starter device cabinet 2 6KV 10KV 400KW Medium voltage Anchorwill High voltage Anchorwill motor Solid state soft starter device cabinet 3 6KV 10KV 400KW Medium voltage Anchorwill High voltage Anchorwill motor Solid state soft starter device cabinet 4
Selection Notes
● Fully understand the characteristics and usage of the load
● The soft starter size should always be larger than the motor current value
● Installation altitude: no more than 1000m (above 1000m requires capacity reduction)