Place of Origin: | China |
Brand Name: | Anchorwill |
Certification: | 3C |
Model Number: | CK70 |
CK70 Built-In Bypass Soft Starter Use DSP Central Processing Unit
ITEM | Project Description | |
Applicable standards | GB14048.6-2016(IEC947-4-2) | |
Applicable motor type | Squirrel-cage three-phase asynchronous motors | |
Motor power | 11A……1260A(5.5~630kW) | |
importation | Control Voltage | AC220V±15%;50Hz/60Hz;AC110V±15% |
Rated Voltage | AC380V±15%;50Hz/60Hz;660V±15% | |
Adjustable start time | 1~120s adjustable | |
Adjustable stopping time | 0~120s adjustable | |
control mode | 1.Ramp voltage 2.Ramp current 3.Current limit mode | |
I/0 | Logic Inputs | 3 channels (X1~X3) |
Analog Outputs | 1 channel 4~20mA/0~10V | |
Relay Output | 2 relay outputs | |
Run the command by typing | Keyboard display unit setting, control terminal setting | |
RS485 communication given. | ||
Communication | Integrated communication protocols | Standard Modbus protocol, 1 channel |
Display Unit | LCD display | Can display current, voltage, alarm and other motor parameters |
Protection and monitoring | Short-circuit, over-voltage, overload, under-voltage, phase loss, over-current, temperature protection | |
Indoor, free from direct sunlight, dust, corrosive, flammable gases, oil mist, water vapor, dripping water or salt. | ||
matrix | Location | Water vapor, dripping water or salt, etc. |
altitude | Altitude more than 1000m, the capacity should be reduced accordingly, every increase of 100m, the current is reduced by 0.5%. | |
environmental temperature | -10℃~+40℃. | |
Above 40℃ shall be used with reduced capacity | ||
For every increase of 1℃, the current shall be reduced by 2%. | ||
Temperature | Less than 95%RH, no water droplet condensation. | |
Vibration | Less than 5.9m/s2(0.6g) | |
Storage Temperature | -40℃~70℃ | |
framework | Protection class | Ip20 |
Cooling method | Radiator, natural cooling | |
Installation | Vertical installation in cabinet |